UCSC Campus Standards Handbook Communications Standards 16700 1
2/17/04
SECTION 16700: COMMUNICATIONS STANDARDS
(NOTE: This Guide Specification incorporates the University’s criteria for communications
cabling. This Section is to be used for development of communication specifications for Contract
Documents. The Design Professional shall be responsible for assuring the specifications are
compatible with the overall design, and are coordinated with all other sections.)
PART 0.00 DESIGN GUIDELINES
0.01 GOALS
A. Data service at standard speeds up to and including 1 Gb/s (IEEE 802.3z standard)
for copper cabling.
B. Voice over IP (VoIP) service capability within five years.
C. Station cabling media types and density to support all communications service for 10+
years. This implies media support for, at minimum, 10 Gb/s full duplex data service on
fiber cabling.
D. Network equipment closet space to allow simultaneous support for two generations of
data service and support parallel voice services from existing and VoIP systems.
E. Network equipment closets to support all communications services for 25 years.
0.02 DEFINITIONS
1. Cable
Horizontal Cable:
Communication cable installed between a Communication Room and a Communication
Plate. Cabling is typically 4-pair copper and/or duplex fiber optic cable.
Intra-Building Backbone Cable:
Communication cable installed between Communication Rooms located in the same
building. Cabling is 25-pair or greater copper and/or multiple strand fiber optic cable.
Inter-Building Backbone Cable
Communication cable installed between Communication Rooms located in different
buildings. Cabling is 25-pair or greater copper and/or multiple strand hybrid fiber optic cable.
2. Communication Room Designations
Ø ADF (Area Distribution Frame):
Ø MDF (Main Distribution Frame):
Page view 0
1 2 3 4 5 6 ... 31 32

Summary of Contents

Page 1 - 2/17/04

UCSC Campus Standards Handbook Communications Standards 16700 1 2/17/04 SECTION 16700: COMMUNICATIONS STANDARDS (NOTE: This Guide Specificatio

Page 2

UCSC Campus Standards Handbook Communications Standards 16700 10 2/17/04 Belden, General Cable, Berk-Tek or equal. b. Horizontal Copper Cable

Page 3

UCSC Campus Standards Handbook Communications Standards 16700 11 2/17/04 h. COPPER CABLE CONNECTORS & TERMINATION HARDWARE 1. Horizontal Co

Page 4

UCSC Campus Standards Handbook Communications Standards 16700 12 2/17/04 Splice connectors shall be 25 pair splicing modules featuring an array o

Page 5

UCSC Campus Standards Handbook Communications Standards 16700 13 2/17/04 Base Horizontal Cable Manager P/N: S188-WD Grounding Kit P/N: S188

Page 6

UCSC Campus Standards Handbook Communications Standards 16700 14 2/17/04 Horizontal fiber optic cables (multimode) must meet the following standar

Page 7 - PART 1.00 GENERAL

UCSC Campus Standards Handbook Communications Standards 16700 15 2/17/04 Outside Plant backbone fiber optic cables shall be rodent resistant armor

Page 8

UCSC Campus Standards Handbook Communications Standards 16700 16 2/17/04 Hubbell P/N: FCR350SP36, Corning, or equal. b. Connector Panels (Quanti

Page 9

UCSC Campus Standards Handbook Communications Standards 16700 17 2/17/04 D. COPPER and FIBER OPTIC CABLE COMMUNICATIONS OUTLET HARDWARE 1. Wal

Page 10

UCSC Campus Standards Handbook Communications Standards 16700 18 2/17/04 Provide complete telecommunications outlet assembly, including but not li

Page 11

UCSC Campus Standards Handbook Communications Standards 16700 19 2/17/04 12 RU (21”) height – Zero PFT P/N: SO2118M or equal. 20 RU (35”) height

Page 12

UCSC Campus Standards Handbook Communications Standards 16700 2 2/17/04 Ø BDF (Building Distribution Frame): Ø IDF (Intermediate Distribution F

Page 13

UCSC Campus Standards Handbook Communications Standards 16700 20 2/17/04 Anixter P/N: 009386, Blackthorn, or equal. 2. Spiral Wrap: clear 0.125

Page 14

UCSC Campus Standards Handbook Communications Standards 16700 21 2/17/04 5. Cable loops and bends shall not have a radius less than that recommen

Page 15

UCSC Campus Standards Handbook Communications Standards 16700 22 2/17/04 E. Support 1. Where drawings specifically allow the installation of c

Page 16

UCSC Campus Standards Handbook Communications Standards 16700 23 2/17/04 a. All horizontal cables shall be trained neatly inside the rear vertica

Page 17

UCSC Campus Standards Handbook Communications Standards 16700 24 2/17/04 e. Termination of Backbone Copper Cable All underground copper backbon

Page 18

UCSC Campus Standards Handbook Communications Standards 16700 25 2/17/04 b. Contractor is responsible for submitting acceptance documentation as

Page 19

UCSC Campus Standards Handbook Communications Standards 16700 26 2/17/04 3. Test Process a. Testing shall be of the Basic Link. The Contractor

Page 20 - PART 3.00 EXECUTION

UCSC Campus Standards Handbook Communications Standards 16700 27 2/17/04 a. Wiremap results that indicate the cabling has no shorts, opens, miss-

Page 21

UCSC Campus Standards Handbook Communications Standards 16700 28 2/17/04 2. The difference between the largest and the smallest resistance readi

Page 22

UCSC Campus Standards Handbook Communications Standards 16700 29 2/17/04 5. For Backbone Fiber Cable, group together the fibers from each binder

Page 23

UCSC Campus Standards Handbook Communications Standards 16700 3 2/17/04 also be included in all copper backbone cabling for campus control and ala

Page 24

UCSC Campus Standards Handbook Communications Standards 16700 30 2/17/04 b. Upon measuring the strand attenuation and verifying that the length o

Page 25

UCSC Campus Standards Handbook Communications Standards 16700 31 2/17/04 Vertical (dB per division) scale factor Horizontal (distance per division

Page 26

UCSC Campus Standards Handbook Communications Standards 16700 32 2/17/04 a. All RJ21 pre-terminated cables shall be labeled with the correspondin

Page 27

UCSC Campus Standards Handbook Communications Standards 16700 4 2/17/04 a. Wall plates shall be located on the walls at a height of 38” to cente

Page 28

UCSC Campus Standards Handbook Communications Standards 16700 5 2/17/04 a. Less than 120 sf 2 research lab plates, and 1 ceiling jack for wirel

Page 29

UCSC Campus Standards Handbook Communications Standards 16700 6 2/17/04 2. All horizontal cable shall be terminated in equipment racks. 3. All

Page 30

UCSC Campus Standards Handbook Communications Standards 16700 7 2/17/04 PART 1.00 GENERAL A. Work shall consist of the provision, installati

Page 31

UCSC Campus Standards Handbook Communications Standards 16700 8 2/17/04 For projects of over 10,000 gross square feet or with estimated communic

Page 32

UCSC Campus Standards Handbook Communications Standards 16700 9 2/17/04 b. The Contractor shall submit a sample of each type of label to be used