UCSC Campus Standards Handbook Communications Standards 16700 1 2/17/04 SECTION 16700: COMMUNICATIONS STANDARDS (NOTE: This Guide Specificatio
UCSC Campus Standards Handbook Communications Standards 16700 10 2/17/04 Belden, General Cable, Berk-Tek or equal. b. Horizontal Copper Cable
UCSC Campus Standards Handbook Communications Standards 16700 11 2/17/04 h. COPPER CABLE CONNECTORS & TERMINATION HARDWARE 1. Horizontal Co
UCSC Campus Standards Handbook Communications Standards 16700 12 2/17/04 Splice connectors shall be 25 pair splicing modules featuring an array o
UCSC Campus Standards Handbook Communications Standards 16700 13 2/17/04 Base Horizontal Cable Manager P/N: S188-WD Grounding Kit P/N: S188
UCSC Campus Standards Handbook Communications Standards 16700 14 2/17/04 Horizontal fiber optic cables (multimode) must meet the following standar
UCSC Campus Standards Handbook Communications Standards 16700 15 2/17/04 Outside Plant backbone fiber optic cables shall be rodent resistant armor
UCSC Campus Standards Handbook Communications Standards 16700 16 2/17/04 Hubbell P/N: FCR350SP36, Corning, or equal. b. Connector Panels (Quanti
UCSC Campus Standards Handbook Communications Standards 16700 17 2/17/04 D. COPPER and FIBER OPTIC CABLE COMMUNICATIONS OUTLET HARDWARE 1. Wal
UCSC Campus Standards Handbook Communications Standards 16700 18 2/17/04 Provide complete telecommunications outlet assembly, including but not li
UCSC Campus Standards Handbook Communications Standards 16700 19 2/17/04 12 RU (21”) height – Zero PFT P/N: SO2118M or equal. 20 RU (35”) height
UCSC Campus Standards Handbook Communications Standards 16700 2 2/17/04 Ø BDF (Building Distribution Frame): Ø IDF (Intermediate Distribution F
UCSC Campus Standards Handbook Communications Standards 16700 20 2/17/04 Anixter P/N: 009386, Blackthorn, or equal. 2. Spiral Wrap: clear 0.125
UCSC Campus Standards Handbook Communications Standards 16700 21 2/17/04 5. Cable loops and bends shall not have a radius less than that recommen
UCSC Campus Standards Handbook Communications Standards 16700 22 2/17/04 E. Support 1. Where drawings specifically allow the installation of c
UCSC Campus Standards Handbook Communications Standards 16700 23 2/17/04 a. All horizontal cables shall be trained neatly inside the rear vertica
UCSC Campus Standards Handbook Communications Standards 16700 24 2/17/04 e. Termination of Backbone Copper Cable All underground copper backbon
UCSC Campus Standards Handbook Communications Standards 16700 25 2/17/04 b. Contractor is responsible for submitting acceptance documentation as
UCSC Campus Standards Handbook Communications Standards 16700 26 2/17/04 3. Test Process a. Testing shall be of the Basic Link. The Contractor
UCSC Campus Standards Handbook Communications Standards 16700 27 2/17/04 a. Wiremap results that indicate the cabling has no shorts, opens, miss-
UCSC Campus Standards Handbook Communications Standards 16700 28 2/17/04 2. The difference between the largest and the smallest resistance readi
UCSC Campus Standards Handbook Communications Standards 16700 29 2/17/04 5. For Backbone Fiber Cable, group together the fibers from each binder
UCSC Campus Standards Handbook Communications Standards 16700 3 2/17/04 also be included in all copper backbone cabling for campus control and ala
UCSC Campus Standards Handbook Communications Standards 16700 30 2/17/04 b. Upon measuring the strand attenuation and verifying that the length o
UCSC Campus Standards Handbook Communications Standards 16700 31 2/17/04 Vertical (dB per division) scale factor Horizontal (distance per division
UCSC Campus Standards Handbook Communications Standards 16700 32 2/17/04 a. All RJ21 pre-terminated cables shall be labeled with the correspondin
UCSC Campus Standards Handbook Communications Standards 16700 4 2/17/04 a. Wall plates shall be located on the walls at a height of 38” to cente
UCSC Campus Standards Handbook Communications Standards 16700 5 2/17/04 a. Less than 120 sf 2 research lab plates, and 1 ceiling jack for wirel
UCSC Campus Standards Handbook Communications Standards 16700 6 2/17/04 2. All horizontal cable shall be terminated in equipment racks. 3. All
UCSC Campus Standards Handbook Communications Standards 16700 7 2/17/04 PART 1.00 GENERAL A. Work shall consist of the provision, installati
UCSC Campus Standards Handbook Communications Standards 16700 8 2/17/04 For projects of over 10,000 gross square feet or with estimated communic
UCSC Campus Standards Handbook Communications Standards 16700 9 2/17/04 b. The Contractor shall submit a sample of each type of label to be used